210 ACH550-UH User’s Manual
Serial Communication – FBA
Data words 5 and 6 are scaled as follows:
Actual Value Mapping
See the users manual supplied with the FBA module.
Generic Profile Technical Data
Overview
The generic profile aims to fulfill the industry-standard drive profile for each protocol
(e.g. PROFIdrive for PROFIBUS, AC/DC Drive for DeviceNet).
Control Word
As described earlier in "Control Interface" the CONTROL WORD is the principal means
for controlling the drive from a fieldbus system. For specific
CONTROL WORD content,
see the users manual provided with the FBA module.
Status Word
As described earlier in "Control Interface", the contents of the STATUS WORD is status
information, sent by the drive to the master station. For specific
STATUS WORD
content, see the users manual provided with the FBA module.
Reference
As described earlier in "Control Interface", the REFERENCE word is a speed or
frequency reference.
Note! REF2 is not supported by the Generic Drive profiles.
Reference Scaling
REFERENCE scaling is fieldbus type specific. However, at the drive, the meaning of a
100%
REFERENCE value is fixed as described in the table below. For a detailed
ABB Drives Profile
Data Word Contents Scaling
5
ACTUAL SPEED -20000 … +20000 = -(par. 1105) … +(par. 1105)
6 TORQUE -10000 … +10000 = -100% … +100%