EasyManua.ls Logo

ABB DriveIT ACH550-UH - Air Flow, 208…240 Volt Drives; Dimensions and Weights

ABB DriveIT ACH550-UH
258 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ACH550-UH User’s Manual 241
Technical Data
Air Flow, 208…240 Volt Drives
The following table lists heat loss and air flow data for 208…240 Volt drives.
Dimensions and Weights
The dimensions and mass for the ACH550 depend on the frame size and enclosure
type. If unsure of frame size, first, find the “Type” code on the drive labels. Then look
up that type code in the "Technical Data" on page 225, to determine the frame size.
A complete set of dimensional drawings for ACH550 drives is located in the ACH550
Technical Reference manual.
-077A-4 R5 1295 4420 168 99
-096A-4 R5 1440
4915 168 99
-124A-4 R6 1940
6621 405 238
-157A-4 R6 2310
7884 405 238
-180A-4 R6 2810 9590 405 238
Drive Heat Loss Air Flow
ACH550-UH- Frame Size W BTU/Hr m
3
/h ft
3
/min
-04A6-2 R1 55 189 44 26
-06A6-2 R1 73
249 44 26
-07A5-2 R1 81 276 44 26
-012A-2 R1 116 404 44 26
-017A-2 R1 161
551 44 26
-024A-2 R2 227 776 88 52
-031A-2 R2 285 373 88 52
-046A-2 R3 420
1434 134 79
-059A-2 R3 536 1829 134 79
-075A-2 R4 671 2290 280 165
-088A-2 R4 786
2685 280 165
-114A-2 R4 1014 3463 280 165
-143A-2 R6 1268 4431 405 238
-178A-2 R6 1575
5379 405 238
-221A-2 R6 1952 6666 405 238
-248A-2 R6 2189 7474 405 238
Drive Heat Loss Air Flow
ACH550-UH- Frame Size W BTU/Hr m
3
/h ft
3
/min

Table of Contents