EasyManua.ls Logo

ABB DriveIT ACH550-UH - Degrees of Protection; Ambient Conditions

ABB DriveIT ACH550-UH
258 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
244 ACH550-UH User’s Manual
Technical Data
Degrees of Protection
Available enclosures:
IP 21 / UL type 1 enclosure. The site must be free of airborne dust, corrosive
gases or liquids, and conductive contaminants such as condensation, carbon
dust, and metallic particles.
IP 54 / UL type 12 enclosure. This enclosure provides protection from airborne
dust and light sprays or splashing water from all directions.
Compared to the IP 21 / UL type 1 enclosure, the IP 54 / UL type 12 enclosure has:
The same internal plastic shell as the IP 21 enclosure
A different outer plastic cover
An additional internal fan to improve cooling.
Larger dimensions
The same rating (does not require a derating).
Ambient Conditions
The following table lists the ACH550 environmental requirements.
Ambient Environment Requirements
Installation Site
Storage and Transportation in the
protective package
Altitude
0…1000 m (0…3,300 ft)
1000…2000 m (3,300…6,600 ft) if
P
N
and I
2
derated 1% every 100 m
above 1000 m (300 ft above 3,300 ft)
Ambient
temperature
-15…40 ºC (5…104 ºF)
Max. 50 ºC (122 ºF) if P
N
and I
2
derated to 90%
-40…70 ºC (-40…158 ºF)
Relative
humidity
< 95% (non-condensing)
Contamination
levels
(IEC 721-3-3)
No conductive dust allowed.
The ACH550 should be installed in
clean air according to enclosure
classification.
Cooling air must be clean, free from
corrosive materials and free from
electrically conductive dust.
Chemical gases: Class 3C2
Solid particles: Class 3S2
Storage
No conductive dust allowed.
chemical gases: Class 1C2
solid particles: Class 1S2
Transportation
No conductive dust allowed.
Chemical gases: Class 2C2
Solid particles: Class 2S2
Sinusoidal
vibration
Mechanical conditions: Class 3M4
(IEC60721-3-3)
2…9 Hz 3.0 mm (0.12 in)
9…200 Hz 10 m/s
2
(33 ft/s
2
)
In accordance with ISTA 1A and 1B
specifications.
Shock
(IEC 68-2-29)
Not allowed max. 100 m/s
2
(330 ft/s
2
), 11ms
(36 fts)

Table of Contents

Related product manuals