ACH550-UH User’s Manual 123
Start-Up
Group 42: External PID
This group defines the parameters used for the second PID controller (PID2) of
ACH550
The operation of parameters 4201…4221 is analogous with Process PID set 1
(PID1) parameters 4001…4021.
Group 42: External PID
Code Description Range Resolution Default S
4201
4221
See 4001 …4021
4228 ACTIVATE -6…12 - 0
Defines the source for enabling the external PID function.
Requires 4230
TRIM MODE = 0 NOT SEL.
0 =
NOT SEL – Disables external PID control.
1 =
DI1 – Defines digital input DI1 as the control for enabling external PID control.
Activating the digital input enables external PID control.
De-activating the digital input disables external PID control.
2…6 =
DI2…DI6 – Defines digital input DI2…DI6 as the control for enabling external PID control.
•See
DI1 above.
7 =
DRIVE RUN – Defines the start command as the control for enabling external PID control.
Activating the start command (drive is running) enables external PID control.
8 = ON – Defines the power-on as the control for enabling external PID control.
Activating power to the drive enables external PID control.
9…12 = TIMER 1…4 – Defines the Timer as the control for enabling external PID control (Timer active enables
external PID control).
See parameter Group 36: Timer Functions.
-1 =
DI1(INV) – Defines an inverted digital input DI1 as the control for enabling external PID control.
Activating the digital input disables external PID control.
De-activating the digital input enables external PID control.
-2…-6 =
DI2(INV)…DI6(INV) – Defines digital input DI2…DI6 as the control for enabling external PID control.
•See
DI1(INV) above.
4229 OFFSET 0.0…100.0% 0.1% 0.0%
Defines the offset for the PID output.
When PID is activated, output starts from this value.
When PID is deactivated, output resets to this value.
Parameter is not active when 4230
TRIM MODE not = 0 (trim mode is active).
4230 TRIM MODE 0…2 1 0
Selects the type of trim, if any. Using the trim it is possible to combine a corrective factor to the drive reference.
0 =
NOT SEL – Disables the trim function.
1 =
PROPORTIONAL – Adds a trim factor that is proportional to the rpm/Hz reference.
2 =
DIRECT – Adds a trim factor based on the control loop’s maximum limit.
4231 TRIM SCALE -100.0%…100.0% 0.1% 0.0%
Defines the multiplier (as a percent, plus or minus) used in the trim mode.