200 ACH550-UH User’s Manual
Serial Communication – FBA
PID Control Setpoint Source
Using the fieldbus for the PID control setpoint requires:
Drive parameter values set as defined below.
Fieldbus controller supplied setpoint value in the appropriate location. (As defined
in
"Analog Output Control" above.)
Communication Fault
When using fieldbus control, specify the drive’s action if serial communication is lost.
Feedback from the Drive – FBA
Inputs to the controller (drive outputs) have pre-defined meanings established by the
protocol. This feedback does not require drive configuration. The following table lists
a sample of feedback data. For a complete listing, see all parameters listed in
"Parameter Descriptions".
Scaling
To scale the drive parameter values see the "Actual Value Scaling" in the following
sections, as appropriate:
Drive Parameter Value Description
Protocol
Reference
4010 SETPOINT SEL 8 (COMM VALUE 1)
9 (
COMM + AI1)
10 (COMM*AI1)
Setpoint is 0135 value (plus or
times AI1)
Drive Parameter Value Description
Protocol
Reference
3018
COMM FAULT
FUNC
0 (NOT SEL)
1 (
FAULT)
2 (
CONST SP7)
3 (LAST SPEED)
Set for appropriate drive
response.
3019 COMM FAULT
TIME
Set time delay before acting on a communication
loss.
Drive Parameter Protocol Reference
0102 SPEED
0103 FREQ OUTPUT
0104 CURRENT
0105 TORQUE
0106 POWER
0107 DC BUS VOLT
0109 OUTPUT VOLTAGE
0301 FB STATUS WORD – bit 0 (STOP)
0301 FB STATUS WORD – bit 2 (REV)
0118 DI1-3 STATUS – bit 1 (DI3)