EasyManua.ls Logo

ABB DriveIT ACH550-UH - Modbus Addressing

ABB DriveIT ACH550-UH
258 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ACH550-UH User’s Manual 157
Serial Communication – EFB
Modbus Addressing
With Modbus, each function code implies access to a specific Modbus reference set.
Thus, the leading digit is not included in the address field of a Modbus message.
Note: The ACH550 supports the zero-based addressing of the Modbus
specification. Holding register 40002 is addressed as 0001 in a Modbus message.
Similarly, coil 33 is addressed as 0032 in a Modbus message.
Refer again to the "Mapping Summary" above. The following sections describe, in
detail, the mapping to each Modbus reference set.
0xxxx Mapping – Modbus Coils. The drive maps the following information to the
0xxxx Modbus set called Modbus Coils:
Bit-wise map of the CONTROL WORD (selected using parameter 5305 EFB CTRL
PROFILE). The first 32 coils are reserved for this purpose.
Relay output states, numbered sequentially beginning with coil 00033.
The following table summarizes the 0xxxx reference set:
Modbus
Ref.
ACH550
Internal Location
(All Profiles)
Standard Profile (ABB DRIVES)
5305
EFB CTRL PROFILE = 0
Alternate Profile (ACH550)
5305 EFB CTRL PROFILE = 1
00001
CONTROL WORD – Bit 0 OFF1* STOP
00002 CONTROL WORD – Bit 1 OFF2* START
00003 CONTROL WORD – Bit 2 OFF3* REVERSE
00004
CONTROL WORD – Bit 3 START LOCAL
00005 CONTROL WORD – Bit 4 N/A RESET
00006 CONTROL WORD – Bit 5 RAMP_HOLD* EXT2
00007 CONTROL WORD – Bit 6 RAMP_IN_ZERO* RUN_DISABLE
00008
CONTROL WORD – Bit 7 RESET STPMODE_R
00009 CONTROL WORD – Bit 8 N/A STPMODE_EM
00010
CONTROL WORD – Bit 9 N/A STPMODE_C
00011
CONTROL WORD – Bit 10 N/A RAMP_2
00012 CONTROL WORD – Bit 11 EXT2 RAMP_OUT_0
00013 CONTROL WORD – Bit 12 N/A RAMP_HOLD
00014
CONTROL WORD – Bit 13 N/A RAMP_IN_0
00015 CONTROL WORD – Bit 14 N/A REQ_LOCALLOCK
00016 CONTROL WORD – Bit 15 N/A TORQLIM2
00017…
00032
Reserved Reserved Reserved
00033 Relay Output 1 Relay Output 1 Relay Output 1
00034 Relay Output 2 Relay Output 2 Relay Output 2
00035 Relay Output 3 Relay Output 3 Relay Output 3
00036 Relay Output 4 Relay Output 4 Relay Output 4

Table of Contents

Related product manuals