158 ACH550-UH User’s Manual
Serial Communication – EFB
* = Active low
For the 0xxxx registers:
• Status is always readable.
• Forcing is allowed by user configuration of the drive for fieldbus control.
• Additional relay outputs are added sequentially.
The ACH550 supports the following Modbus function codes for coils:
1xxxx Mapping – Modbus Discrete Inputs. The drive maps the following
information to the 1xxxx Modbus set called Modbus Discrete Inputs:
• Bit-wise map of the STATUS WORD (selected using parameter 5305 EFB CTRL
PROFILE). The first 32 inputs are reserved for this purpose.
• Discrete hardware inputs, numbered sequentially beginning with input 33.
The following table summarizes the 1xxxx reference set:
00037 Relay Output 5 Relay Output 5 Relay Output 5
00038 Relay Output 6 Relay Output 6 Relay Output 6
Function Code Description
01 Read coil status
05 Force single coil
15 (0x0F Hex) Force multiple coils
Modbus
Ref.
ACH550
Internal Location
(All Profiles)
Standard Profile (
ABB DRIVES)
5305
EFB CTRL PROFILE = 0
Alternate Profile (ACH550)
5305 EFB CTRL PROFILE = 1
10001
STATUS WORD – Bit 0 RDY_ON READY
10002 STATUS WORD – Bit 1 RDY_RUN ENABLED
10003 STATUS WORD – Bit 2 RDY_REF STARTED
10004
STATUS WORD – Bit 3 TRIPPED RUNNING
10005 STATUS WORD – Bit 4 OFF_2_STA* ZERO_SPEED
10006
STATUS WORD – Bit 5 OFF_3_STA* ACCELERATE
10007
STATUS WORD – Bit 6 SWC_ON_INHIB DECELERATE
10008 STATUS WORD – Bit 7 ALARM AT_SETPOINT
10009
STATUS WORD – Bit 8 AT_SETPOINT LIMIT
10010
STATUS WORD – Bit 9 REMOTE SUPERVISION
10011 STATUS WORD – Bit 10 ABOVE_LIMIT REV_REF
10012
STATUS WORD – Bit 11 EXT2 REV_ACT
10013
STATUS WORD – Bit 12 RUN_ENABLE PANEL_LOCAL
10014
STATUS WORD – Bit 13 N/A FIELDBUS_LOCAL
10015 STATUS WORD – Bit 14 N/A EXT2_ACT
Modbus
Ref.
ACH550
Internal Location
(All Profiles)
Standard Profile (
ABB DRIVES)
5305
EFB CTRL PROFILE = 0
Alternate Profile (ACH550)
5305 EFB CTRL PROFILE = 1