ACH550-UH User’s Manual 95
Start-Up
Group 29: Maintenance Trig
This group contains usage levels and trigger points. When usage reaches the set
trigger point, a notice displayed on the control panel signals that maintenance is due.
Group 29: Maintenance Trig
Code Description Range Resolution Default S
2901 COOLING FAN TRIG 0.0…6553.5 kh 0.1 kh 0.0
Sets the trigger point for the drive’s cooling fan counter.
•0.0 =
NOT SEL
2902 COOLING FAN ACT 0.0…6553.5 kh 0.1 kh 0.0
Defines the actual value of the drive’s cooling fan counter.
• The parameter is reset by writing 0.0 to it.
2903 REVOLUTION TRIG 0…65535 MRev 1 MRev 0
Sets the trigger point for the motor’s accumulated revolutions counter.
•0.0 =
NOT SEL
2904 REVOLUTION ACT 0…65535 MRev 1 MRev 0
Defines the actual value of the motor’s accumulated revolutions counter.
• The parameter is reset by writing 0 to it.
2905 RUN TIME TRIG 0.0…6553.5 kh 0.1 kh 0.0
Sets the trigger point for the drive’s run time counter.
•0.0 =
NOT SEL
2906 RUN TIME ACT 0.0…6553.5 kh 0.1 kh 0.0
Defines the actual value of the drive’s run time counter.
• The parameter is reset by writing 0.0 to it.
2907 USER MWh TRIG 0.0…6553.5 MWh 0.1 MWh 0.0
Sets the trigger point for the drive’s accumulated power consumption (in megawatt hours) counter.
•0.0 =
NOT SEL
2908 USER MWh ACT 0.0…6553.5 MWh 0.1 MWh 0.0
Defines the actual value of the drive’s accumulated power consumption (in megawatt hours) counter.
• The parameter is reset by writing 0.0 to it.