ACH550-UH User’s Manual 125
Start-Up
Group 51: Ext Comm Module
This group defines set-up variables for a fieldbus adaptor (FBA) communication
module. For more information on these parameters, refer to the users manualation
supplied with the FBA module.
Group 51: Ext Comm Module
Code Description Range Resolution Default S
5101 FBA TYPE - 1 0
Displays the type of the connected fieldbus adapter module.
0 =
NOT DEFINED – Module not found, or not properly connected, or parameter 9802 is not set to 4 (exT FBA).
1 =
PROFIBUS-DP
16 =
INTERBUS
21 =
LONWORKS
32 =
CANOPEN
37 =
DEVICENET
64 =
MODBUS PLUS
101 =
CONTROLNET
128 =
ETHERNET
5102
5126
FB PAR 2…FB PAR 26 0...65535 1 0
For more information on these parameters, refer to the user’s manual supplied with the FBA module.
5127 FBA PAR REFRESH 0, 1 1 0
Validates any changed fieldbus parameter settings.
After refreshing, the value reverts automatically to DONE.
5128 FILE CPI FW REV 0000…FFFF hex 1 0000 hex
Displays the CPI firmware revision of the drive’s fieldbus adapter configuration file. Format is xyz where:
x = major revision number
y = minor revision number
z = correction number
Example: 107 = revision 1.07
5129 FILE CONFIG ID 0000…FFFF hex 1 0000 hex
Displays the revision of the drive’s fieldbus adapter modules configuration file identification.
File configuration information is drive application program-dependent.
5130 FILE CONFIG REV 0000…FFFF hex 1 0000 hex
Contains the revision of the drive’s fieldbus adapter module configuration file.
Example: 1 = revision 1
5131 FBA STATUS 0…6 1 0
Contains the status of the adapter module.
0 =
IDLE – Adapter not configured.
1 =
EXEC. INIT – Adapter is initializing.
2 =
TIME OUT – A timeout has occurred in the communication between the adapter and the drive.
3 =
CONFIG ERROR – Adapter configuration error.
The major or minor revision code of the adapter’s CPI firmware revision differs from that stated in the drive’s
configuration file.
4 =
OFF-LINE – Adapter is off-line.
5 =
ON-LINE – Adapter is on-line.
6 =
RESET – Adapter is performing a hardware reset.
5132 FBA CPI FW REV 0000…FFFF hex 1 0000 hex
Contains the revision of the module’s CPI program. Format is xyz where:
x = major revision number
y = minor revision number
z = correction number
Example: 107 = revision 1.07