ACH550-UH User’s Manual 217
Diagnostics
Fault Resetting
The ACH550 can be configured to automatically reset certain faults. Refer to
parameter Group 31: Automatic Reset.
Warning! If an external source for start command is selected and it is active,
the ACH550 may start immediately after fault reset.
Flashing Red LED
To reset the drive for faults indicated by a flashing red LED:
• Turn off the power for 5 minutes.
Red LED
To reset the drive for faults indicated by a red LED (on, not flashing), correct the
problem and do one of the following:
• From the control panel, press RESET
• Turn off the power for 5 minutes.
Depending on the value of 1604, FAULT RESET SELECT, the following could also be
used to reset the drive:
• Digital input
• Serial communication
When the fault has been corrected, the motor can be started.
1006 PAR EXT RO Parameter values are inconsistent. Check for the following:
• Extension relay module not connected and
• 1410…1412
RELAY OUTPUTS 4…6 have non-zero values.
1007 PAR FBUS Parameter values are inconsistent. Check for and correct:
• A parameter is set for fieldbus control (e.g. 1001
EXT1 COMMANDS = 10
(
COMM)), but 9802 COMM PROT SEL = 0.
1008 PAR PFAMODE Parameter values are inconsistent – 9904 MOTOR CTRL MODE must be = 3
(
SCALAR: SPEED), when 8123 PFA ENABLE is activated.
1009
PAR PCU 1 Parameter values for power control are inconsistent: Improper motor
nominal frequency or speed. Check for both of the following:
•1 < (60 * 9907 MOTOR NOM FREQ / 9908 MOTOR NOM SPEED < 16
• 0.8 <
9908 MOTOR NOM SPEED /
(120 * 9907
MOTOR NOM FREQ / Motor Poles) < 0.992
1010 PAR PFA
OVERRIDE
Both the override mode and PFA are activated at the same time. These
modes are mutually incompatible, because PFA interlocks cannot be
observed in the override mode.
1011 PAR OVERRIDE
PARS
Overeride is enabled, but parameters are incompatible. Verify that1701 is
not zero, and (depending on 9904 value) 1702 or 1703 is not zero.
Fault
Code
Fault Name In
Panel
Description and Recommended Corrective Action