ACH550-UH User’s Manual 109
Start-Up
5 = THERMISTOR (0) – Sensor configuration uses a thermistor.
Motor thermal protection is activated through a digital input. Connect either a PTC sensor or a normally closed
thermistor relay to a digital input. The drive reads the digital input states as shown in the above table.
When the digital input is ‘0’ the motor is overheated.
See the figures in the introduction to this Group.
6 =
THERMISTOR (1) – Sensor configuration uses a thermistor.
Motor thermal protection is activated through a digital input. Connect a normally open thermistor relay to a digital
input. The drive reads the digital input states as shown in the above table.
When the digital input is ‘1’ the motor is overheated.
See the figures in the introduction to this Group.
3502 INPUT SELECTION 1…8 1 1
Defines the input used for the temperature sensor.
1 =
AI1 – PT100 and PTC.
2 =
AI2 – PT100 and PTC.
3…8 =
DI1…DI6 – Thermistor
3503 ALARM LIMIT -10...200 °C / 1 110 °C /
0...5000 Ohm / 1500 Ohm /
0…1 0
Defines the alarm limit for motor temperature measurement.
At motor temperatures above this limit, the drive displays an alarm (2010,
MOTOR OVERTEMP)
For thermistors:
0 = de-activated
1 = activated
3504 FAULT LIMIT -10...200 °C / 1 130 °C /
0...5000 Ohm / 4000 Ohm /
0…1 0
Defines the fault limit for motor temperature measurement.
At motor temperatures above this limit, the drive displays a fault (9,
MOTOR OVERTEMP) and stops the drive.
For thermistors:
0 = de-activated
1 = activated
Group 35: Motor Temp Meas
Code Description Range Resolution Default S