112 ACH550-UH User’s Manual
Start-Up
3609 STOP DAY 2 1…7 1 1
Defines timer 2 weekly stop day.
See parameter 3605
3610 START TIME 3 00:00:00…23:59:58 2 s 12:00:00
Defines timer 3 daily start time.
See parameter 3602
3611 STOP TIME 3 00:00:00…23:59:58 2 s 12:00:00
Defines timer 3 daily stop time.
See parameter 3603
3612 START DAY 3 1…7 1 1
Defines timer 3 weekly start day.
See parameter 3604
3613 STOP DAY 3 1…7 1 1
Defines timer 3 weekly stop day.
See parameter 3605
3614 START TIME 4 00:00:00…23:59:58 2 s 12:00:00
Defines timer 4 daily start time.
See parameter 3602
3615 STOP TIME 4 00:00:00…23:59:58 2 s 12:00:00
Defines timer 4 daily start time.
See parameter 3603
3616 START DAY 4 1…7 1 1
Defines timer 4 weekly start day.
See parameter 3604
3617 STOP DAY 4 1…7 1 1
Defines timer 4 weekly stop day.
See parameter 3605
3622 BOOST SEL -6…6 1 0
Selects the source for the boost signal.
0 = NOT SEL- Boost signal is disabled.
1 = DI1-Defines DI1 as the boost signal.
2…6 = DI2…DI6 – Defines DI2…DI6 as the boost signal.
-1 = DI1(INV) – Defines an inverted digital input DI1 as the boost signal.
-2…-6 = Defines an inverted digital input DI2…DI6 as the boost signal.
3623 BOOST TIME 00:00:00-23:59:58 2 s 00:00:00
Defines the boost ON time. Time is started
when boost sel signal is released. If parameter
range is 01:30:00, then boost is active for 1
hour and 30 minutes after activation DI is
released.
Group 36: Timer Functions
Code Description Range Resolution Default S
Boost active
Activation DI
Boost time