ACH550-UH User’s Manual 117
Start-Up
4008 0 % VALUE -1000.0…1000.0% 0.1% 0.0%
Defines (together with the next parameter) the scaling applied to the
PID controller’s actual values (PID1 parameters 0128, 0130, and
0132).
Units and scale are defined by parameters 4006 and 4007.
4009 100 % VALUE -1000.0…1000.0% 0.1% 100.0%
Defines (together with the previous parameter) the scaling applied to the PID controllers actual values.
Units and scale are defined by parameters 4006 and 4007.
4010 SET POINT SEL 0…19 1 1 9
Defines the reference signal source for the PID controller.
Parameter has no significance when the PID regulator is by-passed (see 8121
REG BYPASS CTRL).
0 =
KEYPAD – Control panel provides reference.
1 =
AI1 – Analog input 1 provides reference.
2 =
AI2 – Analog input 2 provides reference.
8 =
COMM – Fieldbus provides reference.
9 =
COMM + AI1 – Defines a fieldbus and analog input 1 (AI1) combination as the reference source. See Analog Input
Reference Correction below.
10 = COMM * AI1 – Defines a fieldbus and analog input 1 (AI1) combination as the reference source. See Analog
Input Reference Correction below.
11 = DI3U, 4D(RNC) – Digital inputs, acting as a motor potentiometer control, provide reference.
DI3 increases the speed (the U stands for “up”)
DI4 decreases the reference (the D stands for “down”).
Parameter 2205
ACCELER TIME 2 controls the reference signal’s rate of change.
R = Stop command resets the reference to zero.
NC = Reference value is not copied.
12 =
DI3U, 4D(NC) – Same as DI3U, 4D(RNC) above, except:
Stop command does not reset reference to zero. At restart the motor ramps up, at the selected acceleration rate,
to the stored reference.
13 =
DI5U, 6D(NC) – Same as DI3U, 4D(NC) above, except:
Uses digital inputs
DI5 and DI6.
14 =
AI1 + AI2 – Defines an analog input 1 (AI1) and analog input 2 (AI2) combination as the reference source. See
Analog Input Reference Correction below.
15 =
AI1 * AI2 – Defines an analog input 1 (AI1) and analog input 2 (AI2) combination as the reference source. See
Analog Input Reference Correction below.
16 = AI1 - AI2 – Defines an analog input 1 (AI1) and analog input 2 (AI2) combination as the reference source. See
Analog Input Reference Correction below.
17 =
AI1/AI2 – Defines an analog input 1 (AI1) and analog input 2 (AI2) combination as the reference source. See
Analog Input Reference Correction below.
19 =
INTERNAL – A constant value set using parameter 4011 provides reference.
Group 40: Process PID Set 1
Code Description Range Resolution Default S
Internal scale (%)
P 4009
P 4008
100%
0%
Units (P4006)
Scale (P4007)
-1000%
+1000%