ACH550-UH User’s Manual 133
Start-Up
8117 NR OF AUX MOT 0…3 1 1 9
Sets the number of auxiliary motors.
Each auxiliary motor requires a relay output, which the drive uses to send start/stop signals.
The Autochange function, if used, requires an additional relay output for the speed regulated motor.
The following describes the set-up of the required relay outputs.
Relay Outputs
As noted above, each auxiliary motor requires a relay output, which the drive uses to send start/stop signals. The
following describes how the drive keeps track of motors and relays.
The ACH550 provides relay outputs RO1…RO3.
An external digital output module can be added to provide relay outputs RO4…RO6.
Parameters 1401…1403 and 1410…1412 define, respectively, how relays RO1…RO6 are used – the parameter
value 31 PFA defines the relay as used for PFA.
The ACH550 assigns auxiliary motors to relays in ascending order. If the Autochange function is disabled, the first
auxiliary motor is the one connected to the first relay with a parameter setting = 31 PFA, and so on. If the
Autochange function is used, the assignments rotate. Initially, the speed regulated motor is the one connected to
the first relay with a parameter setting = 31 PFA, the first auxiliary motor is the one connected to the second relay
with a parameter setting = 31 PFA, and so on
The table below shows the ACH550 PFA motor assignments for some typical settings in the Relay Output
parameters (1401…1403 and 1410…1412), where the settings are either =31 (PFA), or =X (anything but 31), and
where the Autochange function is disabled (8118
AUTOCHNG INTERV = 0).
* =One additional relay output for the PFA that is in use.
One motor is in “sleep” when the other is rotating.
Group 81: PFA
Code Description Range Resolution Default S
ACH550
Standard PFA mode
PFA with Autochange mode
ACH550
Relay Logic
Parameter Setting ACH550 Relay Assignment
1
4
0
1
1
4
0
2
1
4
0
3
1
4
1
0
1
4
1
1
1
4
1
2
8
1
1
7
Autochange Disabled
RO1 RO2 RO3 RO4 RO5 RO6
31 X X X X X 1 Aux. X X X X X
31 31 X X X X 2 Aux. Aux. X X X X
31 31 31 X X X 3 Aux. Aux. Aux. X X X
X 31 31 X X X 2 X Aux. Aux. X X X
X X X 31 X 31 2 X X X Aux. X Aux.
3131XXXX1*Aux. Aux. X X X X