ACH550-UH User’s Manual 139
Start-Up
5 = DI5 – Enables the Interlock function, and assigns a digital input (starting with DI5) to the interlock signal for each
PFA relay. These assignments are defined in the following table and depend on:
The number of PFA relays (number of parameters 1401…1403 and 1410…1412) with value = 31 (
PFA).
The Autochange function status (disabled if 8118
AUTOCHNG INTERV = 0, and otherwise enabled).
6 = DI6 – Enables the Interlock function, and assigns digital input DI6 to the interlock signal for the speed regulated
motor.
Requires 8118 AUTOCHNG INTERV = 0.
8121 REG BYPASS CTRL 0…1 1 0
Selects Regulator by-pass control. When enabled,
Regulator by-pass control provides a simple control
mechanism without a PID regulator.
Use Regulator by-pass control only in special
applications.
0 = NO – Disables Regulator by-pass control. The drive
uses the normal PFA reference: 1106
REF2 SELECT.
1 =
YES – Enables Regulator by-pass control.
The process PID regulator is bypassed.
Actual value of PID is used as the PFA reference
(input). Normally
EXT REF2 is used as the PFA
reference.
The drive uses the feedback signal defined by
4014
FBK SEL (or 4114) for the PFA frequency
reference.
The figure shows the relation between the control
signal 4014
FBK SEL (OR 4114) and the speed
regulated motors frequency in a three-motor
system.
Group 81: PFA
Code Description Range Resolution Default S
No. PFA
Relays
Autochange Disabled
(P 8118)
Autochange Enabled
(P 8118)
0
DI1…DI4: Free
DI5: Speed Reg Motor
DI6: Free
Not allowed
1 DI1…DI4: Free
DI5: Speed Reg Motor
DI6: First PFA Relay
DI1…DI4: Free
DI5: First PFA Relay
DI6: Free
2 Not allowed DI1…DI4: Free
DI5: First PFA Relay
DI6: Second PFA Relay
3…6 Not allowed Not allowed
No. PFA
Relays
Autochange Disabled Autochange Enabled
0
DI1…DI5: Free
DI6: Speed Reg Motor
Not allowed
1 Not allowed
DI1…DI5: Free
DI6: First PFA Relay
2…6 Not allowed Not allowed
P 4014
f
MAX
P 8110
P 8109
P 8113
P 8112
A = No auxiliary motors running
B = One auxiliary motor running
C = Two auxiliary motors running
A
f
MIN
B
C
(%)
f
OUT