EasyManua.ls Logo

ABB DriveIT ACH550-UH - Page 236

ABB DriveIT ACH550-UH
258 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
236 ACH550-UH User’s Manual
Technical Data
Longer than 30 m (100 ft) must be limited as specified in the table below. Follow
the instructions in the filter package for all cable screen connections.
Warning! Do not use filters in a floating, or high impedance earthed network.
Cable Requirements for CE Compliance
Drive Type
RFI/EMC Filter
Switching Frequency (Parameter 2606)
1 or 4 kHz (1 or 4) 8 kHz (8)
Maximum motor cable length
ACH550-UH-03A3-4 ACS400-IF11-3 100 m
(330 ft)
Not CE compliant for
more than 30 m
ACH550-UH-04A1-4
ACH550-UH-06A9-4
ACH550-UH-08A8-4
ACH550-UH-012A-4
ACH550-UH-015A-4 ACS400-IF21-3 100 m
(330 ft)
100 m
(330 ft)
ACH550-UH-023A-4
ACH550-UH-031A-4 ACS400-IF31-3 100 m
(330 ft)
100 m
(330 ft)
ACH550-UH-038A-4
ACH550-UH-044A-4 ACS400-IF41-3 100 m
(330 ft)
100 m
(330 ft)
ACH550-UH-059A-4
ACH550-UH-072A-4
ACH550-UH-077A-4
ACH550-UH-180A-4
Not defined at time of publication.