52 ACH550-UH User’s Manual
Start-Up
9905 MOTOR NOM VOLT 230…690 V (US) 1 V 230 V (US) 9
Defines the nominal motor voltage.
Must equal the value on the motor rating plate.
Sets the maximum drive output voltage supplied to the motor.
The ACH550 cannot supply the motor with a voltage greater than the
mains voltage.
9906 MOTOR NOM CURR 0.15*I
2N
…1.5*I
2N
0.1 A 1.5*I
2N
9
Defines the nominal motor current.
Must equal the value on the motor rating plate.
Range allowed: (0.2…2.0) · I
N
(where I
N
is drive current).
9907 MOTOR NOM FREQ 10.0…500 Hz 0.1 Hz 60 Hz (US) 9
Defines the nominal motor frequency.
Range: 10…500 Hz (typically 50 or 60 Hz)
Sets the frequency at which output voltage equals the
MOTOR NOM VOLT.
Field weakening point = Norm freq * Supply Volt / Mot Nom Volt
9908 MOTOR NOM SPEED 50…18000 rpm 1 rpm 1580 rpm (US) 9
Defines the nominal motor speed.
Must equal the value on the motor rating plate.
9909 MOTOR NOM POWER 0.15…1.5*P
N
0.1 Hp 0.2 HP (US) 9
Defines the nominal motor power.
Must equal the value on the motor rating plate.
9910 MOTOR ID RUN 0, 1 1 0 9
This parameter controls a self-calibration process called the
Motor Id Run. During this process, the drive operates the
motor in order to identify it’s characteristics, and then
optimizes control by creating a motor model. This motor
model is especially effective when:
Operation point is near zero speed.
Operation requires a torque range above the motor
nominal torque, over a wide speed range, and without any
measured speed feedback (i.e. without a pulse encoder).
If no Motor Id Run is performed, the drive uses a less
detailed motor model created when the drive is first run. This
“First Start” model is updated automatically* after any motor
parameter is changed. To update the model, the drive
magnetizes the motor for 10 to 15 seconds at zero speed.
*Creating the “First Start model does require that either 9904
= 1 (
VECTOR: SPEED), or 9904 = 3 (SCALAR: FREQ) and
2101 = 3 (
SCALAR FLYSTART) or 5 (FLYSTART + TORQ
BOOST).
Note: Motor models work with internal parameters and user-
defined motor parameters. In creating a model the drive
does not change any user-defined parameters.
0 =
OFF – Disables the Motor Id Run creation process. (Does
not disable the operation of a motor model.)
1 = ON – Enables a Motor Id Run at the next start command.
After run completion, this value automatically changes to
0.
To perform a Motor Id Run:
1. De-couple load from motor (or otherwise reduce
load to near zero).
2. Verify that motor operation is safe:
The run automatically operates the motor in the
forward direction – confirm that forward rotation is
safe.
The run automatically operates the motor at
50…80% of nominal speed – confirm that operation
at these speeds is safe.
3. Check following parameters (if changed from factory
settings):
2001
MINIMUM SPEED < 0
2002
MAXIMUM SPEED > 80% of motor rated speed.
2003
MAX CURRENT > 130% of I
2N
value.
The maximum torque (parameters 2014, 2017 and/
or 2018) > 50%.
4. At the Control Panel, select:
Select Parameters
Select Group 99
Select Parameter 9910
Group 99: Start-up Data
Code Description Range Resolution Default S
Output voltage
Output
P 9907
frequency
P 9905

Table of Contents