ACH550-UH User’s Manual 57
Start-Up
0303 FB STS WORD 1 - 1 - hex
Read-only copy of the Status Word 1.
The drive sends status information to the fieldbus controller. The status consists of two Status Words.
0304 FB STS WORD 2 - 1 - hex
Read-only copy of the Status Word 2.
See parameter 0303.
Group 03: Actual Signals
Code Description Range Resolution Default S
Bit # 0303, STS CMD WORD 1 0304, FB STS WORD 2
0 READY ALARM
1 ENABLED REQ_MAINT
2 STARTED DIRLOCK
3 RUNNING LOCALLOCK
4 ZERO_SPEED CTL_MODE
5 ACCELERATE Reserved
6 DECELERATE Reserved
7 AT_SETPOINT Reserved
8 LIMIT Reserved
9 SUPERVISION Reserved
10 REV_REF REQ_CTL
11 REV_ACT REQ_REF1
12 PANEL_LOCAL REQ_REF2
13 FIELDBUS_LOCAL REQ_REF2EXT
14 EXT2_ACT ACK_STARTINH
15 FAULT ACK_OFF_ILCK