ACH550-UH User’s Manual 59
Start-Up
0308 ALARM WORD 1 - 1 0000 hex
Read-only copy of the
ALARM WORD 1.
When a fault is active, the corresponding bit for the active fault is set in the Fault Words.
Each fault has a dedicated bit allocated within Fault Words.
Bits remain set until the whole alarm word is reset. (Reset by writing zero to the word).
The control panel displays the word in hex. For example, all zeros and a 1 in Bit 0 displays a 0001. All zeros and a
1 in Bit 15 displays as 8000.
0309 ALARM WORD 2 - 1 0000 hex
Read-only copy of the
ALARM WORD 3.
See parameter 0308.
Group 03: Actual Signals
Code Description Range Resolution Default S
* Applies only to HVAC drives.
Bit # 0308, ALARM WORD 1 0309, ALARM WORD 2
0 Reserved Reserved / OFFBUTTON 0*
1 PID SLEEP
2 ID RUN
3 DIR LOCK Reserved
4 I/O COMM
5 AI1 LOSS
6 AI2 LOSS
7 PANEL LOSS
8 Reserved
9 MOT OVERTEMP
10 UNDERLOAD
11 MOTOR STALL
12 AUTORESET
13 AUTOCHANGE
14 PFA INTERLOCK
15 reserved BP LOSS