ACH550-UH User’s Manual 69
Start-Up
-12 = DI1,2,3(INV) – Selects one of seven Constant Speeds (1…7) using DI1, DI2 and DI3.
Inverse operation uses three digital inputs, as defined below (0 =
DI de-activated, 1 = DI activated):
-13 = DI3,4,5(INV) – Selects one of seven Constant Speeds (1…3) using DI3, DI4 and DI5.
See above (
DI1,2,3(INV)) for code.
-14 =
DI4,5,6(INV) – Selects one of seven Constant Speeds (1…3) using DI4, DI5 and DI6.
See above (
DI1,2,3(INV)) for code.
1202 CONST SPEED 1 0…30000 rpm / 1 rpm / 360 (US)/
0.0…500.0 Hz 0.1 Hz 6.0 (US)
Sets value for Constant Speed 1.
The range and units depend on parameter 9904
MOTOR CTRL MODE.
Range: 0…30000 rpm when 9904 = 1 (
VECTOR: SPEED).
Range: 0…500 Hz when 9904 = 3 (
SCALAR: FREQ).
1203 CONST SPEED 2 0…30000 rpm / 1 rpm / 360 (US)/
0.0…500.0 Hz 0.1 Hz 12.0 (US)
Sets a value for a Constant Speed. (See
CONST SPEED 1 above.)
1204 CONST SPEED 3 0…30000 rpm / 1 rpm / 720 (US)/
0.0…500.0 Hz 0.1 Hz 18.0 (US)
1205 CONST SPEED 3 0…30000 rpm / 1 rpm / 1080 (US)/
0.0…500.0 Hz 0.1 Hz 18.0 (US)
Sets a value for a Constant Speed. (See
CONST SPEED 1 above.)
1206 CONST SPEED 3 0…30000 rpm / 1 rpm / 1440 (US)/
0.0…500.0 Hz 0.1 Hz 24.0 (US)
Sets a value for a Constant Speed. (See
CONST SPEED 1 above.)
1207 CONST SPEED 3 0…30000 rpm / 1 rpm / 1800 (US)/
0.0…500.0 Hz 0.1 Hz 30.0 (US)
Sets a value for a Constant Speed. (See
CONST SPEED 1 above.)
1208 CONST SPEED 3 0…30000 rpm / 1 rpm / 2880 (US)/
0.0…500.0 Hz 0.1 Hz 48.0 (US)
Sets a value for a Constant Speed. (See CONST SPEED 1 above.)
1209 TIMED MODE SEL 1…2 1 2 9
Uses the timer(s) specified by parameter 1201, values 15…19, to override the reference defined in Group 11,
Reference Select. This override applies only if the timer function is enabled (parameter 3601).
1 = EXT/CS1/2/3 – The state of the timer(s) specified by param 1201, values 15…19, determines the reference
used. See tables in 1201 at appropriate value.
2 =
CS1/2/3/4 – The state of the timer(s) specified by param 1201, values 15…19, determines the reference used.
See tables in 1201 at appropriate value.
Group 12: Constant Speeds
Code Description Range Resolution Default S
DI1 DI2 DI3 Function
1 1 1 No constant speed
0 1 1 Constant speed 1 (1202)
1 0 1 Constant speed 2 (1203)
0 0 1 Constant speed 3 (1204)
1 1 0 Constant speed 4 (1205)
0 1 0 Constant speed 5 (1206)
1 0 0 Constant speed 6 (1207)
0 0 0 Constant speed 7 (1208)