72 ACH550-UH User’s Manual
Start-Up
35 = COMM – Energize relay based on input from fieldbus communication.
Fieldbus writes binary code in parameter 0134 that can energizes relay 1…relay 6 according to the following:
0 = De-energize relay, 1 = Energize relay.
36 =
COMM(-1) – Energize relay based on input from fieldbus communication.
Fieldbus writes binary code in parameter 0134 that can energizes relay 1…relay 6 according to the following:
0 = De-energize relay, 1 = Energize relay.
37 =
TIMER 1 – Energize relay when timer 1 is activated. See Group 36, Timer Functions.
38…40 = TIMER 2…4 – Energize relay when Timer 2…4 is active. See Timer 1 above.
41 =
M.TRIG FAN – Energize relay when cooling fan counter is triggered.
42 =
M.TRIG REV – Energize relay when revolutions counter is triggered.
43 =
M. TRIG RUN – Energize relay when run time counter is triggered.
44 =
M.TRIG MWH – Energize relay when power consumption counter is triggered.
45 =
OVERRIDE – Energize relay when override is activated.
1402 RELAY OUTPUT 2 0…45 1 2
Defines the event or condition that activates relay 2 – what relay output 2 means.
See 1401
RELAY OUTPUT 1.
1403 RELAY OUTPUT 3 0…45 1 3
Defines the event or condition that activates relay 3 – what relay output 3 means.
See 1401
RELAY OUTPUT 1.
1404 RO 1 ON DELAY 0.0…3600.0 s 0.1 s 0.0 s
Defines the switch-on delay for relay 1.
On / off delays are ignored when relay output 1401 is set to
PFA.
1405 RO 1 OFF DELAY 0.0…3600.0 s 0.1 s 0.0 s
Defines the switch-off delay for relay 1.
On / off delays are ignored when relay output 1401 is set to PFA.
1406 RO 2 ON DELAY 0.0…3600.0 s 0.1 s 0.0 s
Defines the switch-on delay for relay 2.
•See
RO 1 ON DELAY.
Group 14: Relay Outputs
Code Description Range Resolution Default S
Par. 0134 Binary RO6 RO5 RO4 RO3 RO2 RO1
0 000000 0 0 0 0 0 0
1 000001 0 0 0 0 0 1
2 000010 0 0 0 0 1 0
3 000011 0 0 0 0 1 1
4 000100 0 0 0 1 0 0
562 ……………
63 111111 1 1 1 1 1 1
Par. 0134 Binary RO6 RO5 RO4 RO3 RO2 RO1
0 000000 1 1 1 1 1 1
1 000001 1 1 1 1 1 0
2 000010 1 1 1 1 0 1
3 000011 1 1 1 1 0 0
4 000100 1 1 1 0 1 1
562 ……………
63 111111 0 0 0 0 0 0
1404 ON DELAY
1405 OFF DELAY
Control event
Relay status