ACH550-UH User’s Manual 75
Start-Up
1506 FILTER AO1 0…10 s 0.1 s 0.1 s
Defines the filter time constant for
AO1.
The filtered signal reaches 63% of a step change within the time specified.
See figure in parameter 1303.
1507 AO2 CONTENT SEL 99…199 1 104
Defines the content for analog output
AO2. See AO1 CONTENT above.
1508 AO2 CONTENT MIN Depends on selection - 0.0 A
Sets the minimum content value. See
AO1CONTENT MIN above.
1509 AO2 CONTENT MAX Depends on selection - 4.6 A
Sets the maximum content value. See AO1 CONTENT MAX above.
1510 MINIMUM AO2 0.0…20.0 mA 0.1 mA 4.0 mA
Sets the minimum output current. See
MINIMUM AO1 above.
1511 MAXIMUM AO2 0.0…20.0 mA 0.1 mA 20.0 mA
Sets the maximum output current. See
MAXIMUM AO1 above.
1512 FILTER AO2 0.0…10.0 s 0.1 s 0.1 s
Defines the filter time constant for AO2. See FILTER AO1 above.
Group 15: Analog Outputs
Code Description Range Resolution Default S