Parameter Denitions 10-15MN448
Parameters in the Long parameter mode
No. Name/Value Description Default
4016 PI FEEDBACK SIGNAL
SOURCE SELECT
0
0 Analog Input 2(Terminal 4)
1 Analog Input 1(Terminal 6)
2 Motor Current
3 DC Bus voltage
4 Analog 1- Analog 2
5 Largest (Analog 1, Analog 2)
53 COMMUNICATION
PARAMETERS
5302 SERIAL
COMMUNICATIONS
CONFIGURATION
This parameter has three sub settings used to congure the Modbus RTU
Serial Communications. The Sub Parameters are:
Drive Address : Adr 0 to Adr 63
Baud Rate : For Modbus RTU 9.6kbps to 115.2kbps
For CAN Open 125, 250, 500, 1000kbps
Watchdog Timeout : 0 (Disabled, 30, 100, 1000, 3000 milliseconds)
A “t” sufx selects trip on loss of communication. An “r” sufx means that
the drive will coast to stop (output immediately disabled) but will not trip.
Address 1
115.2 kbps
3000 msec
99 START-UP DATA Digital Input Conguration and Motor Data Parameter
9902 DIGITAL INPUTS
FUNCTION SELECT
Denes the function of the digital inputs depending on the control mode
setting in Parameter 1103 PRIMARY COMMAND SOURCE MODE. See
Chapter 9 for detailed examples.
0
Range 0 to 14 See Chapter 9 Control Modes for 9902 parameter selection details
9905 MOTOR (BEMF)
VOLTAGE
This parameter should be set to the rated (nameplate) BEMF voltage of the
motor. See Chapter 2 for information on locating motor nameplate data.
Motor Rating
Dependent
110V/230V rated drives
0…250V
400V rated drives
0…500V
Voltage
Note: The stress on the motor insulation is always dependent on the
drive supply voltage. This also applies to the case where the motor
voltage rating is lower than the rating of the drive and the supply of
the drive.
9906 MOTOR RATED
CURRENT
This parameter should be set to the rated (nameplate) current of the motor.
See Chapter 2 for information on locating motor nameplate data.
Motor Rating
Dependent
0.25*drive rated output
current…1.0*drive rated output
current
Current
9907 MOTOR RATED
FREQUENCY
This parameter should be set to the rated (nameplate) frequency of the
motor. See Chapter 2 for information on locating motor nameplate data.
60Hz
25…500Hz Frequency
9908 MOTOR RATED SPEED This parameter can optionally be set to the rated (nameplate) rpm of the
motor. When set to the default value of zero, all speed related parameters
are displayed in Hz, and the slip compensation for the motor is disabled.
Entering the value from the motor nameplate enables the slip compensation
function, and the DRIVE display will now show motor speed in estimated
rpm. All speed related parameters, such as Minimum and Maximum Speed,
Preset Speeds etc. will also be displayed in RPM.
0 RPM
0…4000 RPM