10-4 Parameter Denitions MN448
10.2 Long Parameter Group
The following tables describes the parameters that are visible in the
PA- mode (Long Group Parameters) that contain a
sequential listing of all available parameters.
Parameters in the Long parameter mode
No. Name/Value Description Default
0000 READ ONLY PARAMETERS
Pressing the NAVIGATE key when the
0000 parameter is displayed will
enter into the Read only status parameter list shown below. Initially 00
is shown and using the UP and DOWN Arrows will scroll to the required
Read only status parameter. Pressing NAVIGATE once more on the will then
display the value of that particular Read only status parameter.
For those parameters which have multiple values (e.g. software ID
parameter 3301), pressing the UP and DOWN keys will display the different
values within that parameter.
Pressing NAVIGATE returns to the next level up. If NAVIGATE is then
pressed again (without pressing UP or DOWN), the display changes to the
next level up (main parameter level, i.e. Parameter “0000”).
Fault history
(read-only)
0102 Rotor Speed
(Estimated)
In vector control mode, this parameter displays the estimated rotor speed
of the motor.
0104 Motor Current 8 most recent values prior to trip, updated every 250ms
0107 DC BUS VOLTAGE Displays the instantaneous DC Bus Voltage internally within the drive in V
DC. (0…1000V dc)
0109 APPLIED MOTOR VOLTAGE Displays the instantaneous output voltage from the drive to the motor V AC.
(0…600V AC)
0110 INTERNAL HEATSINK
TEMPERATURE
Temperature of heatsink in °C (-20 … 100 °C)
0111 SPEED REFERENCE INPUT Displayed in Hz if Parameter 9908 MOTOR RATED SPEED = 0, otherwise
displayed in RPM. (-2008 … 2008)
0115 KWh/MWh METER Total number of KWh/MWh consumed by the drive.
0120 ANALOG INPUT 1 APPLIED
SIGNAL LEVEL
Displays the signal level applied to analog input 1 (Terminal 6) in % after
scaling and offsets have been applied.
0121 ANALOG INPUT 2 APPLIED
SIGNAL LEVEL
Displays the signal level applied to analog input 2 (Terminal 4) in % after
scaling and offsets have been applied.
0126 PI CONTROLLER OUTPUT Displays the output level of the PI controller in %.
0140 HOURS RUN METER Not affected by resetting factory default parameters.
(0 to 99 999 hours)
0150 INTERNAL DRIVE
TEMPERATURE
Actual internal ambient temperature in °C
0160 DIGITAL INPUT STATUS Binary value.
Displays the status of the drive inputs, starting with the left hand side digit
= Digital Input 1 etc.
0183 DC BUS VOLTAGE RIPPLE
LEVEL
Displays the level of ripple present on the DC Bus Voltage in V DC. This
parameter is used by the ACS255 for various internal protection and
monitoring functions.
0188 OPERATING TIME
ACCUMULATED WITH
HEATSINK TEMPERATURE
ABOVE 85°C
Displays the amount of time in hours and minutes that the ACS255 has
operated for during its lifetime with a heatsink temperature in excess of
85°C. This parameter is used by the ACS255 for various internal protection
and monitoring functions. (HH:MM:SS)
0189 OPERATING TIME
ACCUMULATED WITH
AMBIENT TEMPERATURE
ABOVE 80°C
Displays the amount of time in hours and minutes that the DRIVE
has operated for during its lifetime with an ambient temperature in
excess of 80°C. This parameter is used by the DRIVE for various
internal protection and monitoring functions. (HH:MM:SS)