10-16 Parameter Denitions MN448
10.3 Advanced Parameter Group
The following tables describes the parameters that are visible in the PA-A mode (Advanced Parameters).
Parameters in the Long parameter mode
Index Name/Selection Description Default
2017 Maximum Current Limit Denes the max current limit in vector control modes. 110 %
0.1…175.00
2105 DC Injection Speed
Sets the speed at which DC injection current is applied during braking to
Stop, allowing DC to be injected before the drive reaches zero speed if
desired.
0.0 Hz/Rpm
0.0…2008
2106 DC Injection Current
Sets the level of DC injection braking current applied according to the
conditions set in 2104 and 2105.
20 %
0.0…100.0
2301 Vector Mode Gain
Single Parameter for Vector speed loop tuning. Affects P & I terms
simultaneously. Not active when 9903 = 1.
50 %
0.0…200.0
2605 Operating Mode Select
Provides a quick set up to congure key parameters according to the
intended application of the drive. Parameters are preset according to the
table.
Setting Application
Current
Limit (2017)
Torque
Characteristic
(2610 & 2611)
Spin Start
(2101)
0 General 150% Constant 0: Off
1 Pump 110% Variable 0: Off
2 Fan 110% Variable 2: On
2
0: Industrial Mode Intended for general purpose applications.
1: Pump Mode Intended for centrifugal pump applications.
2: Fan Mode Intended for Fan applications.
9903 Motor Control Mode Selects the motor control method. For proper control of the EC
Titanium parameter 9903 should be set to 2 (PM Control).
2
0 Vector speed control mode
1 V/HZ Mode
2 PM Motor Vector Speed Control
3 BLDC Motor Vector Speed Control
9910 Motor parameter
Autotune
WARNING:
Autotune should not
be performed on this
product.
Autotune is disabled in the ECM software however it can be
accessed through the keypad.
In the event an Autotune is performed it will affect performance and
possibly make the IMD inoperable. To recover the motor specic
parameters will need to be loaded. The necessary parameters
and their values can be obtained by scanning the QR Code on the
motor with a smart device or you can access the parameters from
the ECM software under the File menu (allows the parameter set to
be downloaded from the web).
WARNING: Autotune should not be performed on this product.
0: Disable
0: Disable
1: Enable Drive immediately carries out a non-rotating autotune, parameter
9910 MOTOR PARAMETER AUTO-TUNE ENABLE returns to 0
when completed.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB EC Titanium Series and is the answer not in the manual?

ABB EC Titanium Series Specifications

General IconGeneral
BrandABB
ModelEC Titanium Series
CategoryEngine
LanguageEnglish

Related product manuals