Standalone Motor and ABB Drive Setup 11-5MN448
11.6 Start Mode Selection with FASR Motors
Automatic start
With the ACH580 and EC Titanium Motor, it’s recommended to set 21.01 (Vector start mode) = 2 automatic and Parameter
21.03 (Stop mode) = 0 for coast stop. Parameter 21.13 (Autophase mode) should be changed to Turning.
The start of PM motors consists of two parts:
1. Flying start detection: If the motor is rotating, ying start is performed
2. Autophasing detection: If the motor is not rotating, Autophasing is executed after Flying start detection.
After these start routines, the motor is controlled normally with Vector control.
NOTE: Autophasing in this product range is done with DC current injection. The shaft of motor may rotate slightly forward/
backwards during the autophasing, depending on the true orientation of the axis. If axis movement need to be
avoided, then Ramp stop & Post-magnetization may help. In this case drive starts the rotation from same phase from
where the motor was stopped.
Parameter Name Value Description
21.01 Vector start mode
2
Selects the motor start function for the vector motor control
mode, ie. when 99.04 Motor control mode is set to Vector.
Automatic: With permanent magnet motors, start mode
Automatic is recommended. Under Automatic the drive motor
control program identies the ux as well as the mechanical
state of the motor and starts the motor instantly under all
conditions.
Automatic start guarantees optimal motor start in most cases. It
includes the ying start function (starting to control the rotating
motor and accelerating it to the reference speed) and the
automatic restart function (restarting the drive automatically after
a short – max. 10 seconds – power supply failure).
21.03 Stop mode
0
Selects the way the motor is stopped when a stop command is
received.
Coast stop
Stop by switching off the output semiconductors of the drive.
The motor coasts to a stop. It is recommended to use Coast
stop if possible when using the ACH580 with the EC Titanium
motor for best start performance.
When start performance is critical or shaft movement in start need to be minimized apply the following additional settings.
21.03 Stop mode
1
Selects the way the motor is stopped when a stop command is
received.
Ramp stop
Stop along the active deceleration ramp. See parameter
group 23 Speed reference ramp. This mode may be selected
if the application requires a faster stopping time then the
recommended coast to rest mode.
21.08 DC current control Bit 0 = 1
Bit 1 = 1
Bit 0 = 1 Enable DC hold
Bit 1 = 1 Enable post-magnetization
21.09 DC hold speed ~30 rpm Depends on the application and motor, but 30rpm is typically ok
21.10 DC current
reference
~50% Depends on the application and motor, but 50% is typically ok.
21.11 Post -
magnetization
time
~2s Depends on the application and motor, but 2 s is typically ok.