13-4 Troubleshooting MN448
Fault
Code
No. Description Corrective Action
004
0x0B
External trip
(on digital input 3)
E-trip requested on control input terminals. Some settings of parameter 9902
DIGITAL INPUTS FUNCTION SELECT require a normally closed contactor to
provide an external means of tripping the drive in the event that an external
device develops a fault. If a motor thermistor is connected check if the motor
is too hot.
00
0x0C Comms loss trip
Check communication link between drive and external devices. Make sure
each drive in the network has its unique address.
00
0x0E Input phase loss trip Drive intended for use with a 3 phase supply has lost one input phase
SPIn-
0x0F Spin start failed Spin start function failed to detect the motor speed.
00
0x11 Internal memory fault.
Parameters not saved, defaults reloaded.
Try again. If problem recurs, refer to your local ABB representative
000
0x12
Analog input current out
of range
Check input current in range dened by parameter 1300.
00
- Internal drive Fault Refer to your local ABB representative
AUty
- Internal drive Fault Refer to your local ABB representative