Calculated standby cooling setpoint
Occupied cool stpt + offset
Calculated standby heating setpoint
Occupied heat stpt - offset
Calculated shed cooling setpoint.
When the unit is set to an occupied override state
from either UI1 or the CBT Stat, the unit will stay
occupied for this amount of time.
UI1 input configuration.
0 = ZoneTemperature
1 = Occ Sensor
2 = Window Sensor
UI4 input configuration.
0 = CO₂ Sensor
1 = Humidity Sensor
2 = Occ Sensor
4 = Window Sensor
8 = Fan Status
UI2 input configuration.
0 = Offset
1 = Occ Sensor
2 = Window Sensor
UI3 input configuration.
0 = Discharge Air Temp
1 = No Discharge Air Temp
Tune loop gain for cooling and heating
Tune loop integral for cooling and heating
Cooling demand from 0-100%
Heating demand from 0-100%
The calculated cooling setpoint.
The calculated heating setpoint.
If zone temperature is sent thru the network, use
this point.
The active zone temperature. Will show either UI1,
remote temp, or CBT-Stat temperature.
Current strategy version.
The calculated duct heat demand
Saved BACnet point for balanced Kfactor for single
point, or the High Kfactor for 2-point. If Kfactor is
known, write to this point. Set to.1 if not being used.
Approximate altitude for carbon dioxide reading
adjustment.
Percentage of CO₂ signal to override damper
position to maintain
Minimum cooling cfm flow setpoint
Maximum cooling cfm flow setpoint
Maximum heating cfm flow setpoint
Minimum heating cfm flow setpoint
Calculated active flow setpoint.
Minimum fan speed for variable speed fans.
Maximum fan speed for variable speed fans.
Saved BACnet point for balanced Kfactor for low
Kfactor for 2-point. If Kfactor is known, write to this
point.