If active airflow falls below this setpoint, enable the
parallel fan.
Tune loop gain for damper
Tune loop integration for damper
Calculated single point Kfactor, or Hi K factor when
2-point balancing.
Used to override flow setpoints, or to open or close
damper.
0 = Auto
1 = MaxCoolFlowStpt
2 = MinCoolFlowStpt
3 = MaxHeatFlowStpt
4 = MinHeatFlowStpt
5 = Full Open
6 = Full Close (flow setpoint set to -1)
Calculated Lo K factor when 2-point balancing.
Calculated shed heating setpoint.
Commands the box to occupied or unoccupied
mode.
0 = Unoccupied Mode
1 = Occupied Mode
2 = Standby Mode
Minimum CO₂ range for a 0-10V input
Maximum CO₂ range for a 0-10V input
The maximum amount of time for value travel from
0-100%
Override the box to another control mode:
0 = Auto
1 = Morning Warm Up
2 = Morning Cool Down
4 = Heat Only
8 = Cool Only
16 = Fire
32 = Purge
Step time for value. If
TriStateTravelTime
is 120
seconds and Min on time is 10 seconds, there are 12
equal steps between 0 and 100% for the valve.
Current HVAC mode status of the unit.
0 = Auto
1 = Morning Warm Up
2 = Morning Cool Down
4 = Heat Only
8 = Cool Only
16 = Shed
32 = Fire
64 = Purge
Used for input reset. Not for BACnet use.
Network point to send outdoor air temperature to
box.
Network point to send AHU supply air temperature
to box
The current position of the damper
The box will shed active setpoints based on a 0-
100% signal.