Used for input reset. Not for BACnet use
graphic_VariableFanSignal
Used for graphics. Analog variable fan signal.
Shows current occupancy status.
0=Unocc
1=Occ
3=Standby
4=SetbackMode
8=SetupMode
Shows current heating/cooling status of the box:
1=CoolMode
2=VentMode
4=HeatMode
Used for graphics. Analog variable heat signal.
Maximum temperature of duct discharge air temp
setpoint when dual max control is off.
Used for graphics. Analog variable heat signal.
Available for AHU outdoor air reset of the damper.
PID gain tuned for duct heat.
The outdoor air temperature that the perimeter
heat will be locked out.
The calculated perimeter heat demand
Custom low output voltage value for AO14 if
stg1OutType
set to 4
Custom high output voltage value for AO14 if
stg1OutType
set to 4
Custom low output voltage value for AO15 if
stg2OutType
set to 4
Custom high output voltage value for AO15 if
stg2OutType
set to 4
Time in minutes the digital heartbeat needs to
change to maintain communication status.