56 Modbus/TCP Start-up
21 TIMEOUT MODE Selects which Modbus/TCP register accesses
reset the timeout counter.
2 =
Control
RW
ACS355:
FB PAR 21
ACSM1:
FBA PAR21
ACS850/ACQ810:
FBA par21
ACS880/ACS580:
Timeout mode
0 = None The Modbus/TCP timeout feature is disabled.
1 = Any message The timeout counter is reset when any Modbus
register of the drive is accessed.
2 = Control RW The timeout counter is reset when the drive
receives either a new Control word or new
reference value (REF1 or REF2) from the
Modbus/TCP client.
22 WORD ORDER Selects in which order the 16-bit registers of
32-bit parameters are transferred.
For each register (16-bit), the first byte contains
the high order byte and the second byte
contains the low order byte.
1 = HILO
ACS355:
FB PAR 22
ACSM1:
FBA PAR22
ACS850/ACQ810:
FBA par22
ACS880/ACS580:
Word order
0 = LOHI The first register contains the low order word
and the second register contains the high order
word.
1 = HILO The first register contains the high order word
and the second register contains the low order
word.
23
26
Reserved These parameters are not used by the adapter
module when the module is configured for
Modbus/TCP.
N/A