EasyManua.ls Logo

ABB FENA-01 - Page 57

ABB FENA-01
388 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Modbus/TCPStart-up 57
27 FBA PAR
REFRESH
Validates any changed adapter module
configuration parameter settings. After
refreshing, the value reverts automatically to
0 = Done.
Note: This parameter cannot be changed while
the drive is running.
0 = Done
ACS355/ACSM1:
FBA PAR
REFRESH
ACS850/ACQ810:
FBA par refresh
ACS880/ACS580:
FBA A/B par
refresh
0 = Done Refreshing done
1 = Refresh Refreshing
28 PAR TABLE VER Read-only. Displays the parameter table
revision of the fieldbus adapter module
mapping file stored in the memory of the drive.
In format xyz, where
x = major revision number
y = minor revision number
z = correction number
OR
in format axyz, where
a = major revision number
xy = minor revision numbers
z = correction number or letter.
N/A
ACS355:
FILE CPI FW REV
ACSM1:
PAR TABLE VER
ACS850/ACQ810:
Par table ver
ACS880/ACS580:
FBA A/B par table
ver
Parameter table revision
29 DRIVE TYPE
CODE
Read-only. Displays the drive type code of the
fieldbus adapter module mapping file stored in
the memory of the drive.
N/A
ACS355:
FILE CONFIG ID
ACSM1:
DRIVE TYPE
CODE
ACS850/ACQ810:
Drive type code
ACS880/ACS580:
FBA A/B drive type
code
Drive type code of the fieldbus adapter module
mapping file
No. Name/Value Description Default