58 Modbus/TCP Start-up
30 MAPPING FILE
VER
Read-only. Displays the fieldbus adapter
module mapping file revision stored in the
memory of the drive in decimal format.
N/A
ACS355:
FILE CONFIG REV
ACSM1:
MAPPING FILE
VER
ACS850/ACQ810:
Mapping file ver
ACS880/ACS580:
FBA A/B mapping
file ver
Mapping file revision
31 D2FBA COMM STA Read-only. Displays the status of the fieldbus
adapter module communication.
Note: The value names may vary by drive.
0 = Idle
OR
4 = Off-
line
ACS355:
FBA STATUS
ACSM1:
D2FBA COMM STA
ACS850/ACQ810:
D2FBA comm sta
ACS880/ACS580:
D2FBA A/B comm
status
0 = Idle Adapter is not configured.
1 = Exec.init Adapter is initializing.
2 = Time out A timeout has occurred in the communication
between the adapter and the drive.
3 = Conf.err Adapter configuration error: The major or minor
revision code of the common program revision
in the fieldbus adapter module is not the
revision required by the module or mapping file
upload has failed more than three times.
4 = Off-line Adapter is off-line.
5 = On-line Adapter is on-line.
6 = Reset Adapter is performing a hardware reset.
No. Name/Value Description Default