Modbus/TCP – Start-up 65
5102 FB PAR 2
(PROTOCOL/PROFILE)
1 (= MB/TCP ABB E) Selects the Modbus/TCP
protocol and the ABB Drives -
Enhanced profile.
5103 FB PAR 3
(COMMRATE)
0 (= Auto)
2)
Ethernet communication rate is
negotiated automatically by the
device.
5104 FB PAR 4
(IP CONFIGURATION)
0 (= Static IP) Configuration will be obtained
from parameters 05…13.
5105 FB PAR 5
(IP ADDRESS 1)
192
2)
First part of the IP address
5106 FB PAR 6
(IP ADDRESS 2)
168
2)
Second part of the IP address
5107 FB PAR 7
(IP ADDRESS 3)
0
2)
Third part of the IP address
5108 FB PAR 8
(IP ADDRESS 4)
16
2)
Last part of the IP address
5109 FBA PAR 9
(SUBNET CIDR)
24
2)
Sets the network mask as
255.255.255.0, allowing access
only to the last subnet.
5120 FB PAR 20
(MODBUS/TCP
TIMEOUT)
10
2)
Sets the communication timeout
as 1 second.
5121 FB PAR 21
(TIMEOUT MODE)
2 (= Control RW)
2)
The timeout feature monitors the
updating of the Control word and
Reference 1.
3018 COMM FAULT
FUNC
1 = FAULT
2)
Enables fieldbus communication
fault monitoring.
3019 COMM FAULT TIME 3.0 s
2)
Defines the fieldbus
communication break
supervision time.
5401 FBA DATA IN 1 106
2)
Power
5402 FBA DATA IN 2 107
2)
DC bus voltage
5501 FBA DATA OUT 1 1202
2)
Constant speed 1
5502 FBA DATA OUT 2 1203
2)
Constant speed 2
5127 FBA PAR REFRESH 1 = REFRESH Validates the FENA-01/-11/-21
configuration parameter
settings.
Drive parameter Setting for ACS355
drives
Description