voltage inversion phenomenon may occur also on remote end of adjacent lines.
Distance protection of such line must have built-in functionality which applies
normally to protection of series compensated lines.
It usually takes a bit of a time before the spark gap flashes, and sometimes the fault
current will be of such a magnitude that there will not be any flashover and the
negative impedance will be sustained. If equation
122 is valid
11 11
< < +
C S
X X X X
EQUATION1898 V1 EN (Equation 122)
in figure 124, the fault current will have the same direction as when the capacitor is
bypassed. So, the directional measurement is correct but the impedance measured is
negative and if the characteristic crosses the origin shown in figure
124 the IED cannot
operate. However, if there is a memory circuit designed so it covers the negative
impedance, a three phase fault can be successfully cleared by the distance protection.
As soon as the spark gap has flashed the situation for protection will be as for an
ordinary fault. However, a good protection system should be able to operate correctly
before and after gap flashing occurs.
en06000625.vsd
jX
R
X
11
X
12
X
C
Z
S
IEC06000625 V1 EN
Figure 124: Cross-polarized
quadrilateral
characteristic
en06000584_small.vsd
jX
R
X
11
X
12
X
C
Z
S
X
F
W
X
R
V
R
FW
R
RV
IEC06000584-SMALL V1 EN
Figure 125: Quadrilateral
characteristic with
separate impedance and
directional measurement
If the distance protection is equipped with an earth-fault measuring unit, the negative
impedance occurs when
1_11 0 _11
3 2× > × +
C
X X X
EQUATION1919 V1 EN
(Equation 123)
Cross-polarized distance protection (either with mho or quadrilateral characteristic)
will normally handle earth-faults satisfactory if the negative impedance occurs inside
the characteristic. The operating area for negative impedance depends upon the
Section 8 1MRK 502 071-UEN -
Impedance protection
244 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062