OperationZ1, OperationZ2: With the settingsOperationZ1 and OperationZ2 each
zone can be set On or Off.
For the two zones the impedance settings are made as shown in figure 151.
R
X
Z1 or Z2
-XoffsetZ1 or -XoffsetZ2
Z1diameter or Z2diameter
IEC06000460_2_en.vsd
IEC06000460 V2 EN
Figure 151: Impedance settings for the fast (Z1) and slow (Z2) zone
The impedances are given in pu of the base impedance calculated according to
equation 171.
EQUATION1776 V1 EN (Equation 171)
XoffsetZ1
and XoffsetZ2, offset of impedance circle top along the X axis, are given
negative value if X < 0.
XoffsetZ1: It is recommended to set XoffsetZ1= - X
d
'/2 and Z1diameter = 100% of
ZBase.
Section 8 1MRK 502 071-UEN -
Impedance protection
288 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual