Table 68: General settings parameters for the Measurement function
Setting Short description Selected
value
Comment
Operation
Operation
Off
/
On On
Function must be
On
PowAmpFact
Amplitude factor to scale power
calculations
1.000 Typically no scaling is required
PowAngComp
Angle compensation for phase
shift between measured I & U
180.0 Typically no angle compensation
is required. However here the
required direction of P & Q
measurement is towards busbar
(Not per IED internal default
direction). Therefore angle
compensation have to be used in
order to get measurements in
aliment with the required
direction.
Mode
Selection of measured current
and voltage
L1L2 Only UL1L2 phase-to-phase
voltage is available
k Low pass filter coefficient for
power measurement, U and I
0.00 Typically no additional filtering is
required
UGenZeroDb Zero point clamping in % of
Ubase
25 Set minimum voltage level to 25%
IGenZeroDb Zero point clamping in % of Ibase 3 Set minimum current level to 3%
UBase (set in
Global base)
Base setting for voltage level in
kV
35.00 Set LV side rated phase-to-phase
voltage
IBase (set in
Global base)
Base setting for current level in A 495 Set transformer LV winding rated
current
SBase (set in
Global base)
Base setting for power in MVA 31.5 Set based on rated power
Measurement function application for a generator
Single line diagram for this application is given in figure
311.