220kV Busbar
300/1
15/ 0,1kV
4000/5
100 MVA
242/15,65 kV
Yd5
U
L1L2
, U
L2L3
G
P Q
100MVA
15,65kV
IEC09000041-1-en.vsd
IED
IEC09000041-1-EN V1 EN
Figure 311: Single line diagram for generator application
In order to measure the active and reactive power as indicated in figure 311, it is
necessary to do the following:
1. Set correctly all CT and VT data and phase angle reference channel
PhaseAngleRef using PCM600 for analog input channels
2. Connect, in PCM600, measurement function to the generator CT & VT inputs
3. Set the setting parameters for relevant Measurement function as shown in the
following table:
Section 17 1MRK 502 071-UEN -
Monitoring
634 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual