EasyManua.ls Logo

ABB Relion 615 series - Page 34

ABB Relion 615 series
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Panel cut-out of 167 x 203 mm with mounting holes
Depth behind the panel 107 mm
When IP 54 degree of protection (according to IEC 60529) is required for the
front side, a gasket has to be used in the installation.
1. Mount the angle frame into the panel cut-out with four M4 screws.
A
B
C
D
E
F
G
H
A070586 V4 EN
Figure 12: Mounting the angled frame
A
177 ±0.3 mm
B 167 ±1 mm
C 203 ±1 mm
D 40.5 mm
E 122 mm
F 40.5 mm
G ∅ 5.5 mm
H 190 mm
2. Loosen the four M5 fixing screws in the case to fit the case into the angle frame.
3. Mount the case to the angle frame.
With the angled frame, the IED can be mounted inclined downward to a 25°
angle.
4. Tighten the screws.
The allowed range for the fixing screws’ tightening torque is
0.7...1 Nm.
5. Install the plug-in unit into the case.
Section 4 1MRS756375 K
Mounting
26 615 series
Installation Manual

Table of Contents