4.3.10 Replacing a Strömberg SP_J40 series relay by a 615
series IED
1.
Drill new screw holes (4.5 mm) to the panel according to the dimensional
drawing.
E
C
D C
B
A
GUID-C7CA77AA-74EA-40D2-B98E-84735BCADDA2 V1 EN
Figure 25: Screw hole and existing panel cut-out dimensions for
replacing a SP_J40 series IED
A
442 mm
B 183 mm
C 150 mm
D 152 mm
E 194 mm
2. Mount the installation plate to the existing panel cut-out with M5 thread
forming screws.
Section 4 1MRS756375 K
Mounting
38 615 series
Installation Manual