EasyManua.ls Logo

ABB RELION 670 SERIES REG670 - Setting Guidelines

ABB RELION 670 SERIES REG670
830 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
L1
(A)
L2
(B)
L3
(C)
Protected Object
CT 1500/5
Star/Wye
Connected
7
8
9
10
11
12
1
2
3
4
5
6
AI01 (I)
AI02 (I)
AI03 (I)
AI04 (I)
AI05 (I)
AI06 (I)
6
IED
X1
R1
1
2
4 5
V
R2
1
3
4
2
1 2 3
N
1-Ph Plate with Metrosil and Resistor
2
3
5
4
N
L1
(A)
L2
(B)
L3
(C)
CT 1500/5
1
ANSI09000170-5-en.vsdx
SMAI2
BLOCK
REVROT
^GRP2_A
^GRP2_B
^GRP2_C
^GRP2_N
G2AI3P
G2AI1
G2AI2
G2AI3
G2AI4
G2N
ANSI09000170 V5 EN-US
Figure 61: CT connections for restricted earth fault protection
Pos Description
1 Scheme grounding point
Ensure that only one grounding point exists in this scheme.
2 One-phase plate with stabilizing resistor and metrosil. Protective ground is a separate 4 mm screw
terminal on the plate.
3 Necessary connection for the metrosil.
4 Position of optional test switch for secondary injection into the high impedance differential IED.
5 Necessary connection for stabilizing resistor.
6 How to connect the high impedance restricted earth fault protection scheme to one CT input in IED.
7.2.4 Setting guidelines
IP14945-1 v1
M13076-3 v2
The setting calculations are individual for each application. Refer to the dif
ferent
application descriptions below
.
Section 7 1MRK 502 071-UUS A
Differential protection
166 Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062