17.5.3 Setting guidelines
IP14841-1 v1
M12811-3 v3
The input parameters for the Event function (EVENT) can be set individually via the
local HMI (Main Menu/Settings / IED Settings /
Monitoring / Event Function) or
via the Parameter Setting Tool (PST).
EventMask
(Ch_1 - 16)
M12811-5 v3
The inputs can be set individually as:
NoEvents
OnSet, at pick-up of the signal
OnReset, at drop-out of the signal
OnChange, at both pick-up and drop-out of the signal
AutoDetect, the EVENT function makes the reporting decision (reporting criteria
for integers have no semantic, prefer to be set by the user)
LONChannelMask
or
SPAChannelMask
M12811-15 v2
Definition of which part of the event function block that shall generate events:
Disabled
Channel 1-8
Channel 9-16
Channel 1-16
MinRepIntVal
(1 - 16)
M12811-29 v3
A time interval between cyclic events can be set individually for each input channel.
This can be set between 0 s to 3600 s in steps of 1 s. It should normally be set to 0, that
is, no cyclic communication.
M12811-34 v1
It is important to set the time interval for cyclic events in an optimized
way to minimize the load on the station bus.
17.6 Disturbance report DRPRDRE
IP14584-1 v2
1MRK 502 071-UUS A Section 17
Monitoring
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062 699