EasyManua.ls Logo

ABB RELION 670 SERIES REG670 - System Grounding

ABB RELION 670 SERIES REG670
830 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
heavily distorted signals. These faults are handled with outmost security and
dependability, although sometimes with reduced operating speed.
8.3.2.1 System grounding
GUID-FC9BF10E-8CA1-4B23-887D-2EAB6A2A0A6E v1
The type of system
grounding plays an important role when designing the protection
system. Some hints with respect to distance protection are highlighted below.
Solidly grounded networks
GUID-6870F6A8-EB28-47CF-AF26-7CE758BF934E v1
In solidly grounded systems, the transformer neutrals are connected directly to ground
without any impedance between the transformer neutral and ground.
ANSI05000215 V2 EN-US
Figure 95: Solidly grounded network
The ground-fault current is as high or even higher than the short-circuit current. The
series impedances determine the magnitude of the fault current. The shunt admittance
has very limited influence on the ground-fault current. The shunt admittance may,
however, have some marginal influence on the ground-fault current in networks with
long transmission lines.
The ground-fault current at single phase-to-ground in phase A can be calculated as
equation
76:
A A
0
1 2 0 f 1 N f
3 V
3I
Z Z Z 3Z Z Z Z
V×
= =
+ + + + +
EQUATION1710 V2 EN-US (Equation 76)
Where:
VA is the phase-to-ground voltage (kV) in the faulty phase before fault.
Z
1
is the positive sequence impedance (Ω/phase).
Z
2
is the negative sequence impedance (Ω/phase).
Z
0
is the zero sequence impedance (Ω/phase).
Z
f
is the fault impedance (Ω), often resistive.
Z
N
is the ground-return impedance defined as (Z
0
-Z
1
)/3.
1MRK 502 071-UUS A Section 8
Impedance protection
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062 229
Application manual

Table of Contents

Related product manuals