ABB RELION 670 SERIES REG670 - Interlocking for Breaker-And-A-Half Diameter BH (3); Application

ABB RELION 670 SERIES REG670
830 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
989_OP = 1
989_CL = 0
989G_OP = 1
989G_CL = 0
If, in this case, line voltage supervision is added, then rather than setting 989 to open
state, specify the state of the voltage supervision:
989_OP = VOLT_OFF
989_CL = VOLT_ON
If there is no voltage supervision, then set the corresponding inputs as follows:
VOLT_OFF = 1
VOLT_ON = 0
15.3.9 Interlocking for breaker-and-a-half diameter BH (3)
IP14173-1 v3
15.3.9.1 Application
M13570-3 v6
The interlocking for breaker-and-a-half diameter (BH_CONN(3), BH_LINE_A(3),
BH_LINE_B(3)) functions are used for lines connected to a breaker-and-a-half
diameter according to figure
280.
Section 15 1MRK 502 071-UUS A
Control
594 Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Application manual