Figure 253: Busbars divided by bus-section disconnectors (circuit breakers)
The project-specific logic for input signals concerning bus-coupler are the same as the
specific logic for the line bay (ABC_LINE):
Signal
BC_12_CL A bus-coupler connection exists between busbar WA1 and WA2.
VP_BC_12 The switch status of BC_12 is valid.
EXDU_BC No transmission error from bus-coupler bay (BC).
The logic is identical to the double busbar configuration “Signals from bus-coupler“.
15.3.4.3
Configuration setting
M13566-22 v5
If there are no second busbar B and therefore no
289 disconnector, then the
interlocking for 289 is not used. The state for 289, 2189G, BC_12 are set to open by
setting the appropriate module inputs as follows. In the functional block diagram, 0 and
1 are designated 0=FALSE and 1=TRUE:
289_OP = 1
289QB2_CL = 0
2189G_OP = 1
2189G_CL = 0
BC_12_CL = 0
VP_BC_12 = 1
Section 15 1MRK 502 071-UUS A
Control
574 Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Application manual