ABB RELION 670 SERIES REG670 - Setting the Reach with Respect to Load

ABB RELION 670 SERIES REG670
830 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
( )
( )
( ) ( )
2 2
0 Im
Im 0
Re Im
X m B
K
B B
×
=
+
EQUATION1428 V2 EN-US (Equation 62)
Parallel line is out of service and grounded in both ends
GUID-345B36A6-B5FB-46DD-B5AE-81A1599FFC6E v1
Apply the same measures as in the case with a single set of setting parameters. This
means that an underreaching zone must not overreach the end of a protected circuit for
the single phase-to-ground faults.
Set the values of the corresponding zone (zero-sequence resistance and reactance)
equal to:
R
0E
R
0
1
X
m0
2
R
0
2
X
0
2
+
--------------------------
+
è ø
ç ÷
æ ö
×=
EQUATION561 V1 EN-US (Equation 63)
X
0E
X
0
1
X
m0
2
R
0
2
X
0
2
+
--------------------------
è ø
ç ÷
æ ö
×=
EQUATION562 V1 EN-US (Equation 64)
8.2.3.6 Setting the reach with respect to load
GUID-ED84BDE6-16CD-45ED-A45D-5CFB828A9040 v6
Set separately the expected fault resistance for phase-to-phase faults RFPPZx and for
the phase-to-ground faults RFPGZx for each zone. For each distance zone, set all
remaining reach setting parameters independently of each other
.
The final reach in the resistive direction for phase-to-ground fault loop measurement
automatically follows the values of the line-positive and zero-sequence resistance, and
at the end of the protected zone is equal to equation 65.
( )
1
R 2 R1 R0 RFPG
3
= × + +
ANSIEQUATION2303 V1 EN-US (Equation 65)
2X1Zx X0Zx
arctan
2 R1Zx R0Zx
loop


EQUATION2304 V2 EN-US (Equation 66)
Section 8 1MRK 502 071-UUS A
Impedance protection
220 Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Application manual