EasyManua.ls Logo

ABB RELION 670 SERIES REG670 - Settings from PCM600

ABB RELION 670 SERIES REG670
830 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GUID-CD4EB23C-65E7-4ED5-AFB1-A9D5E9EE7CA8 V3 EN
GUID-CD4EB23C-65E7-4ED5-AFB1-A9D5E9EE7CA8 V3 EN-US
Figure 328: Settings for IEC 60870-5-103 communication
The general settings for IEC 60870-5-103 communication are the following:
SlaveAddress and BaudRate: Settings for slave number and communication speed
(baud rate).
The slave number can be set to any value between 1 and 254. The communication
speed, can be set either to 9600 bits/s or 19200 bits/s.
RevPolarity: Setting for inverting the light (or not). Standard IEC 60870-5-103
setting is Enabled.
CycMeasRepTime: See I103MEAS function block for more information.
EventRepMode: Defines the mode for how events are reported. The event buffer
size is 1000 events.
Event reporting mode
If EventRepMode = SeqOfEvent, all GI and spontaneous events will be delivered in the
order they were generated by BSW. The most recent value is the latest value delivered.
All GI data from a single block will come from the same cycle.
If EventRepMode = HiPriSpont, spontaneous events will be delivered prior to GI
event. To prevent old GI data from being delivered after a new spontaneous event, the
pending GI event is modified to contain the same value as the spontaneous event. As a
result, the GI dataset is not time-correlated.
20.5.2.2 Settings from PCM600
M17109-132 v2
I103USEDEF
GUID-A41170D6-2846-4E5E-8B7F-85B53D4EF6B6 v1
For each input of the I103USEDEF function there is a setting for the information
number of the connected signal. The information number can be set to any value
between 0 and 255. To get proper operation of the sequence of events the event masks
in the event function is to be set to ON_CHANGE. For single-command signals, the
event mask is to be set to ON_SET.