Figure 319: High-availability Seamless Redundancy (HSR)
19.2.3 Setting guidelines
GUID-887B0AE2-0F2E-414D-96FD-7EC935C5D2D8 v1
Redundant communication is configured with the Ethernet configuration tool in
PCM600.
Redundancy: redundant communication is activated when the parameter is set to
PRP-0, PRP-1 or HSR. The settings for the next access point will be hidden and
PhyPortB will show the second port information. Redundant communication is
activated after a common write to IED is done.
PRP-1 should be used primarily, PRP-0 is intended only for use in existing PRP-
networks. PRP-1 and HSR can be combined in a mixed network.
If the access point is not taken into operation, the write option in Ethernet
Configuration Tool can be used to activate the access point.
1MRK 502 071-UUS A Section 19
Ethernet-based communication
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062 739
Application manual