EasyManua.ls Logo

ABB RELION 670 SERIES REG670 - Page 228

ABB RELION 670 SERIES REG670
830 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2
load min
Z
V
S
=
EQUATION1718 V1 EN-US (Equation 69)
Where:
V the minimum phase-to-phase voltage in kV
S the maximum apparent power in MVA.
The load impedance [Ω/phase] is a function of the minimum operation voltage and the
maximum load current:
min
load
ma x
Z
V
3 I
=
×
EQUATION1719 V1 EN-US (Equation 70)
Minimum voltage V
min
and maximum current I
max
are related to the same operating
conditions. Minimum load impedance occurs normally under emergency conditions.
As a safety margin, it is required to avoid load encroachment under
three-phase conditions. To guarantee correct healthy phase IED
operation under combined heavy three-phase load and ground faults
both phase-to-phase and phase-to-ground fault operating characteristics
should be considered.
To avoid load encroachment for the phase-to-ground measuring elements, the set
resistive reach of any distance protection zone must be less than 80% of the minimum
load impedance.
load
RFP G 0.8 Z£ ×
EQUATION1720 V1 EN-US (Equation 71)
This equation is applicable only when the loop characteristic angle for the single
phase-to-ground faults is more than three times as large as the maximum expected
load-impedance angle.
For the case when the loop characteristic angle is less than three
times the load-impedance angle, more accurate calculations are necessary according to
equation
72.
Section 8 1MRK 502 071-UUS A
Impedance protection
222 Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Application manual

Table of Contents

Related product manuals