Figure 105: Example of tapped line with Auto transformer
This application gives rise to a similar problem that was highlighted in section
Fault
infeed from remote end, that is increased measured impedance due to fault current
infeed. For example, for faults between the T point and B station the measured
impedance at A and C will be:
ZA =ZAT + ·ZTF
IA + IC
IA
DOCUMENT11524-IMG3509 V3 EN-US (Equation 97)
A C
2
C Trf CT TB
C
I I V2
Z Z (Z Z ) ( )
V1
I
+
= + + × ×
EQUATION1714 V1 EN-US (Equation 98)
Where:
Z
AT
and Z
CT
is the line impedance from the A respective C station to the T point.
I
A
and I
C
is fault current from A respective C station for fault between T and B.
Table continues on next page
1MRK 502 071-UUS A Section 8
Impedance protection
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062 243
Application manual